GDSF-411WPD 3-in-1 SF6 Gas Analyzer(with pump)

GDSF-411WPD 3-in-1 SF6 Gas Analyzer(with pump)

Brief Description:

GDSF-411WPD 3-in-1 SF6 Gas Analyzer is combined of SF6 humidity (dew point) test, SF6 purity test and SF6 gas decomposition product test. It integrates the functions that can only be achieved with three instruments in one instrument. One-time on-site measurement can complete the detection of all indexes, which greatly saves the gas in the equipment, at the same time reduces the workload of users and improves work efficiency.

 

 


Product Detail

Product Tags

Application

• Analysis of trace moisture, purity, and decomposition products of SF6 gas electrical equipment for electric power

• SF6 gas cylinder gas quality test

• Quality test of SF6 gas for recovery and reuse

• High purity gas manufacturing

• Semiconductor industry dry gas supply

• Research and development use

• Clean room/dry house monitoring

• Metal heat treatment site and laboratory industrial gas humidity detection, such as air, CO2, N2, H2, O2, SF6, He, Ar and other inert gases.

Features

•With self-calibration function, ensure the stability and reliability of moisture, purity, and decomposition detection data throughout the year.

• All gas path with high polymer material design, ensures no water wall hanging phenomenon and guarantees the test speed.

•The oil-free stainless-steel body regulating valve is used to ensure the accuracy of the measured value.

• Advanced software algorithms improve the test accuracy of sensors.

•Combined chassis configuration solution, users can easily combine related instruments and accessories. The overall package is carried, which makes the user have a more relaxed experience.

• Start-up test, no need to preheat and oscillate.

•Temperature conversion and pressure data correction.

• Fuzzy computing technology.

• High-power lithium battery power, realize AC and DC dual power supply. No on-site AC power is required. Lithium battery power supply continues to work for more than 8 hours without the need of an external power supply.

• Anti-electromagnetic interference circuit design to ensure product reliability.

• Large-capacity memory, which can realize 1000 sets of data storage functions.

•The test data is stable and can provide both standard dew point values and converted dew point values at 20℃.

• Purity measurement accuracy is 0.5% in the full range. It can be applied to the measurement of high concentration SF6 gas and 70% content SF6 gas.

• The best test flow area shows that the user can adjust the gas flow intuitively and quickly. Reduce test time.

• The air inlet is designed with a miniature self-sealing joint, and the air path to be tested will not leak when the air path is disconnected.

•With internal pump, to pump back SF6 gas to stored cylinder.

Specifications

•Measurement method: Resistive and Capacitive measurement principle

• Measurement range: dew point -80℃--+20℃ (support ppmv)

• Accuracy: ±2℃

(when the dew point temperature is below 0 ℃, the sensor output is the frost point)

• Response time: 63% [90%]

+20→-20℃ Td 5s[45s]

-20→-60℃ Td 10s[240s]

• Resolution: 0.01℃

• Repeatability: ± 0.5 ℃

•Display unit: ℃, ppm, ℃P20(converted value at 20℃)

• Gas flow: 400-600mL/min

• Flow display: 0-1000mL digital flow meter

•Sample gas pressure: ≤1MPa

SF6 Purity

•Measurement method: Infrared Measurement Principle (NDIR series sensors)

• Measuring range: 0 ~ 100% SF6

•Response time: [90%] 60s

•Accuracy: ± 0.5%FS

• Repeatability: ± 0.5%

•Resolution: 0.01%

•Display unit: %

• Gas flow: 300-450mL/min

SF6 Decomposition Products

• Measurement method: Electrochemical Measurements Principle (Electrochemical series sensors)

•Measurement range: H2S: 1 ~ 200ppmv      SO2: 1~ 100ppmv

• Accuracy: H2S: 10ppmv ±3%     SO2: 10ppmv ±3%

•Repeatability: H2S: 10ppmv ±2%   SO2: 10ppmv ±2%

• Sensitivity: 0.5ppmv

• Display unit: ppmv

•Gas flow: 250-300mL/min

•Pump back function: recycling chamber 2L, recycling time ≤ 5min, with gas drying function (For option)

• Oxygen pressure: ≤1Mpa

• Probe protection: stainless steel sintered filter

• Power supply: 110-220VAC, 50Hz, AC/DC use, over-charge protection, continuous working is no lower than 8hours.

• Use environment temperature: -20--+60℃

• Environment humidity: 90%RH

• Measurement value influence: No effect of pressure and flow

• Dimension: 570*420*280mm

•Weight: about 14kg.